Preliminary datasheet · Rev 0.1Certification in progress
BDC125K
125 kW bidirectional power conversion system for battery energy storage
Links a battery string to the 415 V three-phase LT network. Its SiC stage charges and discharges on EMS command while controlling active and reactive power at the point of connection.
- Rated power
- 125 kW / 125 kVA
- AC connection
- 415 V, 3-phase
- Battery voltage
- 650–950 V DC
- Peak efficiency
- 98.9 %
Application
Where it sits in your site
BDC125K connects on the 415 V LT bus, behind the site's own transformer and meter. Sensitive or 4-wire loads use an external isolation transformer.
Utility grid11 kV
Transformer11 kV / 415 V
Meter
415 V LT bussite loads
Isolation transformeroptional
BDC125K125 kW PCS
Battery650–950 V DC
Communication
EMS ↔ BDC125K · Modbus RTU
BMS ↔ BDC125K · isolated CAN
Specifications
Technical parameters
| Operating voltage | 650–950 V |
|---|---|
| Max. DC voltage | 1000 V |
| Max. DC current | 200 A |
| Rated power | 125 kW / 125 kVA |
|---|---|
| Grid connection | 3-phase, 3-wire + PE |
| Rated voltage | 415 V line-to-line |
| Voltage range | 360–460 V |
| Rated current | 190 A |
| Frequency | 50 Hz (47.5–52 Hz)* |
| Power factor | −1 to +1 |
| Current THD | < 3 % at rated power* |
| Topology | 2-level, 3-leg SiC MOSFET active front end |
|---|---|
| Grid filter | LCL with active damping |
| Isolation | Transformerless; external isolation transformer for 4-wire loads |
| Peak efficiency | 98.9 % |
| Cooling | Forced air, temperature-controlled |
| Dimensions (W × H × D) | 520 × 750 × 250 mm |
|---|---|
| Enclosure | IP20 |
| Operating temperature | −20 to +60 °C, derating above 55 °C |
| Relative humidity | 0–95 %, non-condensing |
| Altitude | ≤ 2000 m without derating |
| BMS interface | Isolated CAN |
|---|---|
| EMS interface | Modbus RTU |
| Grid code | Designed to IS 16169, EN 50549, IEEE 1547 and CEA connectivity standards |
|---|---|
| Safety / EMC | IEC 62477-1; IEC 61000-6-2 / -6-4* |
| Certification | In progress |
* Design target. Specifications are subject to change without notice.
Downloads
Documents for your engineering team
Sizing a PCS for your BESS project?
Share your battery voltage, capacity and site details. We'll recommend a configuration and send a budgetary quote.
Or write to jitendra@zealev.com · +91 95600 17169